====OPC-UA Driver=== ===Information=== OPC-UA is the replacement for the older **OPC-DA** standard. ^Driver Info^Detail^ |Driver Type:|**Live Only**| |Platforms:|**All**| ===Driver Settings=== This driver has two options. ^Option^Description^ |Address|The address of the OPC-UA host machine, including the port number| |Namespace|The ID of the namespace node (usually **2** or **3**)| ===Point Settings=== OPC-UA points only have one setting - the **full address** of the point. This is made up of a path of objects seperated by a slash (/) symbol, then a period (.) between the last object and its property. UA points for a hierarchy - for instance, you might have a UA object called the **Main Motor**, which contains a **Cooling System** which in turn has a property called **Outlet Temperature**. The final UA point name would be... Main Motor/Cooling System.Outlet Temperature ===Performance Note=== Some OPC-UA servers only support specific parts of the OPC-UA standard. For this reason, the ARDI OPC-UA drivers use a slower but much more reliable search method when connecting. This makes the //connection// phase quite slow when you have large UA servers. However, once the connection is completely stablished, OPC-UA is one of the fastest-update methods available, and has the least impact on your network. This is because OPC-UA is a //subscription// protocol - it only transmits **changes** to your data rather than needing to be constantly re-polled.